logo
russian english german
 

RemTEK-03 Electric Drive

Explosion-proof multiturn RemTEK-03 electric drives with electronic torque and position limitation are aimed to regulate pipeline valves and fittings with diameter from 100 to 1200 mm, in explosion hazardous areas of class 1 and 2 as per GOST P 51330.9-99 in severe operating conditions with the extended ambient temperature ranges (from minus 60 to plus 50 °С).    

   

Application - Shut-off and control valves, stop valves (wedge valves, sliding shutter etc), including emergency shutdown system (ESD).

   

There are three basic modifications of Rem-TEK-03 electric drive being manufactured as per ways of control and power supply:

  • on the basis of BUR control module (S type) with in-built noncontact reversing-type starter and smooth start function
  • on the basis of BUR control module (M type) with external reversing-type starter and smooth start function
  • on the basis of BUR control module (R type) with external reversing-type starter and smooth start function

Basic Functions

 
   
  • Pipeline valves control with switching off as per position and torque
  • Smooth start (S and M types of control modules)
  • Dynamic braking mode with accurate stops in any position (S type of control module)
  • Complete protection of the electric motor
  • Digital signaling and control
  • Control by in-built desk or remote control panel
  • Internal interfaces RS-485 (Modbus RTU and Profibus DP) and CAN
  • Analog valve position signal (4...20mA)

Technical Parameters: 

 

Explosion protection marking

1ExdIIBT4

Protection class

IP67

Ambient temperature, °C

from -60 to +50

R, M modifications control module supply voltage, V

220
(-50%, +47%)

S modification control module and all electric drives modifications power circuits supply voltage , V

380
(-50%, +47%)

  

Features 

 
  • RemTEK-03 electric drive includes BUR control module with SCR's control for electric motor smooth start and dynamic braking with setting up torque limitation in three zones: start, moving and stopping
  • Torque measuring and limiting with the help of in-built algorithms as per measured electric motor parameters
  • Setting up ESD and fire systems trip points
  • Auxiliary output terminal for electric drive external testing or emergency change-over to the desired position (ESD system, fire system)

Main Modifications of RemTEK-03 Electric Drives

 

Modification

Type
of mounting
seat

Rotation
torque
ranges, N·m

Output
element
rate at the torque
50 % out of max., rpm

Capacity
of electric motor,
kW

Rated
amperage, А

Maximum
amperage, А

RemTEK-03.B.3000.30.5.X

B

30…300

30

0,55

1,8

10,8

RemTEK-03.B.3000.60.5.X

B

30…300

60

1,1

2,7

17,6

RemTEK-03.B.600.40.5.X

B

60...600

40

1,5

5,2

33,8

RemTEK-03.B.600.40.5.X

C

60...600

40

1,5

5,2

33,8

RemTEK-03.C.800.96.5.X

C

80...800

96

5,5

12,5

90

RemTEK-03.C.1000.20.5.X

C

100...1000

20

1,5

4,7

22,6

RemTEK-03.C.1000.48.5.X

C

100...1000

48

4

8,5

59,5

RemTEK-03.D.4000.15.5.X

D

400...4000

15

4

11

78,8

RemTEK-03.D.5000.7.5.5.X

D

500...5000

7,5

2,5

5,6

29,5

RemTEK-03.D.5000.15.5.X

D

500...5000

15

5,5

12,5

90

RemTEK-03.E.7000.12.5.X

E

700...7000

12

5,5

12,5

90

RemTEK-03.E.10000.6.5.X

E

1000...10000

6

4

8,5

59,5

RemTEK-03.E.10000.12.5.X

E

1000...10000

12

7,5

14,8

111

X - control module modification (R, M, S) depending on the way of motor control

 

Components

 

- Electric drive control module BUR

- Electric motor AIM-A and DATEK-250

- Hand wheeled gearbox

- Valves adapters (if necessary)

 

Auxiliary Equipment

 

- Communication unit MKS-07М

- Communication unit PI-04Т

Remote Control Panel

 
Certificates and Permits